Minor or dynamic pressure loss in pipe or tube system components can be expressed as
Δ p minor_loss = ξ ρf v 2 / 2 (1)
Δ p minor_loss = minor pressure loss (Pa (N/m 2 ), psf (lb/ft 2 ) )
v = flow velocity (m/s, ft/s)
Minor loss coefficients for commonly used pipe and tube system components:
Type of Component or Fitting | Minor Loss Coefficient - ξ - |
---|---|
Tee, Flanged, Dividing Line Flow | 0.2 |
Tee, Threaded, Dividing Line Flow | 0.9 |
Tee, Flanged, Dividing Branched Flow | 1.0 |
Tee, Threaded, Dividing Branch Flow | 2.0 |
Union, Threaded | 0.08 |
Elbow, Flanged Regular 90 o | 0.3 |
Elbow, Threaded Regular 90 o | 1.5 |
Elbow, Threaded Regular 45 o | 0.4 |
Elbow, Flanged Long Radius 90 o | 0.2 |
Elbow, Threaded Long Radius 90 o | 0.7 |
Elbow, Flanged Long Radius 45 o | 0.2 |
Return Bend, Flanged 180 o | 0.2 |
Return Bend, Threaded 180 o | 1.5 |
Globe Valve, Fully Open | 10 |
Angle Valve, Fully Open | 2 |
Gate Valve, Fully Open | 0.15 |
Gate Valve, 1/4 Closed | 0.26 |
Gate Valve, 1/2 Closed | 2.1 |
Gate Valve, 3/4 Closed | 17 |
Swing Check Valve, Forward Flow | 2 |
Ball Valve, Fully Open | 0.05 |
Ball Valve, 1/3 Closed | 5.5 |
Ball Valve, 2/3 Closed | 200 |
Diaphragm Valve, Open | 2.3 |
Diaphragm Valve, Half Open | 4.3 |
Diaphragm Valve, 1/4 Open | 21 |
Water meter | 7 |
The minor loss a ball valve with flow velocity 2 m/s with water with density 1000 kg/m 3 can be calculated as
Δ p minor_loss = (5.5) (1000 kg/m 3 ) (2 m/s) 2 / 2